395CAV - Flashing Code 33

Carrier Gas Furnaces: 395CAV

Re: Flashing Code 33 / Fault Code 33

Flash Sequence = 3 Short Flashes + 3 Long Flashes (- - - , — — —)

Code 33 = Open Limit or Roll-Out

The Primary Limit is wired in series with other limits, including up to two Roll-out Switches or a Fusible-Link roll-out switch.

Therefore, a Fault Code 33 can be caused by one of the following:

► If the limit circuit stays open for more than 3 minutes, the code changes to Code 13.


Qty Possible Causes:
Dirty Filter
1 Clogged Evaporator Coil
Restricted Ductwork
Bad Heat Exchanger
Bad Limit Switch
Excessive Gas Pressure
Bad Control Board

CHECKOUT:

1. Check Furnace Operation


2. Check Blower Motor


3. Check Temperature Rise


4. Check Gas Pressure


5. Check Duct Static Pressure


6. Check Limit Circuit