York Heat Pumps: YHJF

Re: Heating - High Electric Bill

When the customers reports an electric bill that is much higher than normal, that typically means that the auxiliary heaters are operating more than normal.

► The blower and auxiliary heaters are typically working normally or the customer would also be experiencing no heat.


Qty Possible Causes:
2 Refrigerant Charge
1 Bad Expansion Valve
No Power to O/D Unit
Bad Capacitor
Control in Lockout
1 Compressor Problem
Defrost Problem
Thermostat Issue
1 Ductwork Problem
Bad Control Board


CHECKOUT:

1. Check Unit Status & Power


2. Check Compressor Operation


3. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

4. Check Compressor Discharge Temperature


5. Check Air Temperature Rise


6. Check Thermostat Aux Settings (New VisionPro 8000)