Climatemaster Geothermal: TS060 / TT064 / TE064
Re: Performance Chart
The following chart shows the design operating conditions of the heat pump WITH THE HWG OFF and operating at FULL CAPACITY.
► The chart is based on 3 GPM/Ton and 70° Return Air Temperature.
COOLING | ||||||
EWT | Suction | Discharge | Superheat | Subcool | Water Rise | Air Drop |
60° | 129-139 | 241-261 | 21-26 | 12-17 | 9.7-11.7 | 22-28 |
70° | 133-143 | 276-296 | 15-20 | 11-16 | 10-12 | 22-28 |
80° | 136-146 | 320-340 | 13-18 | 11-16 | 9.7-11.7 | 21-27 |
90° | 138-148 | 364-384 | 10-15 | 11-16 | 9.5-11.5 | 21-27 |
100° | 141-151 | 416-436 | 9-14 | 12-17 | 9.3-11.3 | 20-26 |
110° | 142-152 | 469-489 | 8-13 | 12-17 | 9-11 | 20-26 |
HEATING | ||||||
EWT | Suction | Discharge | Superheat | Subcool | Water Drop | Air Rise |
30° | 72-82 | 289-309 | 10-16 | 10-15 | 4-6 | 20-26 |
40° | 81-91 | 302-322 | 10-16 | 11-16 | 4.8-6.8 | 23-29 |
50° | 99-109 | 316-336 | 11-17 | 12-17 | 5.7-7.7 | 26-32 |
60° | 113-123 | 330-350 | 11-17 | 13-18 | 6.5-8.5 | 28-34 |
70° | 126-136 | 345-365 | 12-18 | 15-20 | 7.3-9.3 | 30-37 |