Climatemaster Geothermal: TS036 / TT038 / TE038
Re: Performance Chart
The following chart shows the design operating conditions of the heat pump WITH THE HWG OFF and operating at FULL CAPACITY.
► The chart is based on 3 GPM/Ton and 70° Return Air Temperature.
COOLING | ||||||
EWT | Suction | Discharge | Superheat | Subcool | Water Rise | Air Drop |
60° | 133-143 | 231-241 | 7-12 | 12-17 | 10.1-12.1 | 19-25 |
70° | 135-145 | 265-285 | 7-12 | 12-17 | 10-12 | 19-25 |
80° | 138-148 | 307-327 | 7-12 | 12-17 | 9.6-11.6 | 19-25 |
90° | 140-150 | 349-369 | 8-13 | 8-13 | 9.3-11.3 | 17-23 |
100° | 143-153 | 398-418 | 8-13 | 8-13 | 9.1-11.1 | 17-23 |
110° | 145-155 | 447-467 | 8-13 | 8-13 | 9-11 | 17-23 |
HEATING | ||||||
EWT | Suction | Discharge | Superheat | Subcool | Water Drop | Air Rise |
30° | 76-86 | 300-320 | 7-12 | 14-19 | 4.5-6.5 | 19-25 |
40° | 90-100 | 315-335 | 8-13 | 16-21 | 5.4-7.4 | 21-27 |
50° | 105-115 | 331-351 | 10-15 | 17-22 | 6.4-8.4 | 24-30 |
60° | 120-130 | 345-365 | 11-16 | 18-23 | 7.3-9.3 | 27-34 |
70° | 135-145 | 364-384 | 11-16 | 19-24 | 8.2-10.2 | 30-37 |