Heat Pump - Flashing Code 2 (Cooling)

York Heat Pump: Yorkguard IV & Yorkguard V

Re: Flashing Code 2 (Cooling)

Code 2 = High Discharge Pressure

If the Hi Pressure circuit input on the Yorkguard opens, the module will go into a Code 2 lockout and disable compressor operation.


Qty Possible Causes (Cooling):
Bad Capacitor
Bad Cond Fan Motor
Refrigerant Overcharge
Mis-Sized Fan Blades
Bad Pressure Switch
Dirty Outdoor Coil
Bad Defrost Relay


CHECKOUT:

1. Check Unit Operation


2. Check O/D Motor & Capacitor


3. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 55-75 Deg O/D 75-95 Deg O/D
R-22
  • 55-70 Suction
  • 150-225 Discharge
  • 55-80 Suction
  • 175-270 Discharge
R410A
  • 100-135 Suction
  • 250-320 Discharge
  • 120 -150 Suction
  • 300 - 450 Discharge