WSH - Defrost Problem / Outdoor Coil Frozen

Trane Rooftop Heat Pump: WSH

Re: Not Defrosting / Frozen

This model uses a Reliatel RTRM module to control defrost.

The board uses an Ambient (outdoor) Sensor and Liquid Line Sensor to determine the proper conditions for defrost to occur.


Qty Possible Causes:
1 Bad Liquid Line Sensor
Bad Condenser Fan Motor
Bad Fan Capacitor
Bad RTRM
Low Refrigerant Charge
Bad Expansion Valve
Bad Fan Relay


CHECKOUT:

1. Check Outdoor Fan


2. Test Defrost Cycle

TEST MODE STEPS
Step 1 Indoor Fan
Step 2 Economizer Open
Step 3 Cool Stage 1
Step 4 Cool Stage 2
Step 5 Heat Stage 1
Step 6 Heat Stage 2
Step 7 Heat Stage 3
Step 8 Defrost
Step 9 Emergency Heat

3. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R-22
  • 20-50 Suction
  • 150-250 Discharge
  • 55-70 Suction
  • 175-275 Discharge

4. Check Liquid Line Sensor


5. Check Ambient (Outdoor) Sensor

​​​​​​​