York Heat Pump
Re: 331-01975-102 DEMAND DEFROST CONTROL
Issue: Outdoor Unit Won't Come On
The Demand-Defrost control has a selectable defrost curve. The original board is programmed at the factory with the correct defrost settings for the unit on which it is installed. The factory-programmed board is set on defrost curve "P".
- Replacement defrost controls have no program, but the control comes out of the box set on "P".
What to do:
- The jumper pin MUST be placed in a numbered position. (The most common is position "2")
- If the jumper is missing or in the "P" position, the replacement control will not energize the compressor.
- Use Pin Position 1 for reciprocating compressors and Pin Position 2 for Scroll compressors.
- Do not use Pin Positions 3 or 4 unless instructed to do so by Tech Support.
- When the jumper position is changed, the control will not act upon the jumper change until the thermostat calls are de-energized or 24V power to the control is cycled.