Rheem Gas Furnace: R95PA
Re: Status & Fault Codes
The furnace control comes standard with a 7-segment diagnostic display.
During Standby mode (with no faults), the display will read "0".
During normal Heating, Cooling or Continuous Fan operation, a letter will be displayed to describe the mode of operation:
| Code | Description |
| 0 | Standby - No Faults |
| C | Compressor On - Cooling or Heat Pup |
| H | Gas Heat On |
| F | Continuous Fan On |
| 10 | 1 Hour Lockout |
| 11 | Failed Ignition |
| 12 | Low Flame Signal |
| 13 | Flame Lost |
| 14 | Unexpected Flame |
| 20 | Twinning Error |
| 22 | Main Limit or HALC tripped |
| 26 | Reversed Polarity |
| 33 | Roll-Out Open |
| 55 | Pressure Switch Closed When it Should be Open |
| 57 | Pressure Switch Open When it Should be Closed |
| 58 | Water Sensed |
| 61 | Blower Fault |
| 93 | Internal Control Fault |
FAULT RECALL
Upon power reset, the three most recent faults which are less than one week old will be flashed in succession from the most recent to the oldest. After one week, a fault will be removed from the fault buffer.
MANUAL FAULT CLEAR
Faults will automatically be cleared from the fault buffer after one week. The fault buffer can also be manually cleared if this is desired. For the first 30 seconds after a change in state of dipswitch SW4, the furnace control will wait to determine if the switch becomes on/off/on/off/on/off or off/on/off/on/off/on within 30 seconds. When this action is detected within 30 seconds, the fault code memory buffer shall be cleared. Be sure to return the dipswitch to the original state (on or off) or is in the desired position after clearing the fault buffer using this method.
5-Minute Lockout
A five minute “soft” lockout will be initiated if the pressure switch fails to close after 60 seconds of continuous inducer operation at the beginning of a normal heat cycle (pressure switch proving period). The seven-segment display will display the appropriate fault. Lockout will automatically be reset after five minutes.
1-Hour Lockout
A one hour “soft” lock out will be initiated when:
The seven-segment display will alternately display “10” and the code number for the fault causing the lockout. Lockout will automatically be reset after one hour.
Hard Lockout
Three conditions shall cause a hard lockout: