T755 Configuration

PRO1 Thermostat: T755

Re: Installer Setup Options

To enter Installer Setup:

  1. Press the "MENU" button.
  2. Press and hold the "TECH SETUP" button for 3 seconds.
  3. Use the PREV and NEXT keys to move between setup items.
  4. Use the + and - key to change options.
  5. Press the "DONE" key to exit.
Setup Function Options
FILTER Filter Change Reminder
  • OF = Off, no filter reminder (default setting
  • 50 to 2000 hours (50 hour increments)
CALIBRATE Room temperature Calibration
  • 0 = 0 deg (defaut0
  • -4 to + 4 deg adjustable
COOL SWING

Cool Swing/Cool Cycle Rate

  • 0.5 = 0.5 deg (default)
  • 0.2 to 2.0 deg adjustable
HEAT SWING

Heat Swing/Heat Cycle Rate

  • 0.4 = 0.4 deg (default)
  • 0.2 to 2.0 deg adjustable
PTAC MODE PTAC Mode
  • ON = Allows multiple fan speeds (default)
  • OFF = 1 fan speed only
PTAC FAN SPEEDS

Fan Speed Mode

G = Low, O/B = Med, Y2 = High

  • 1 = On, Auto
  • 2 = Low, High, Auto (default)
  • 3 = Low, Med, High, Auto
PTAC MED SPEED

Medium Speed Selection

O or B

  • O = O terminal (default)
  • B = B terminal
HEAT PUMP Heat Pump Mode
  • OF = Off, Conventional heat (default)
  • ON = Heat Pump mode activated
SET STAGES # of Heat / Cool Stages
  • 1H / 1C = 1 Heat, 1 Cool
  • 2H / 1C = 2 Heat, 1 Cool
  • 2H / 2C = 2 Heat, 2 Cool
  • 3H / 1C = 3 Heat, 1 Cool
  • 3H / 2C = 3 Heat, 2 Cool
  • 4H / 2C = 4 Heat, 2 Cool
SYSTEM SET Set System Mode Options
  • HEAT OFF COOL (default)
  • HEAT OFF
  • COOL OFF
  • HEAT OFF COOL AUTO
DUAL FUEL Dual Fuel Heat Pump Option
  • OF = Off (default)
  • ON = On 
FAN SET Heating Fan Operation
  • GAS = No fan with heat (default)
  • ELECTRIC = Fan on with heat
SS STAGING

Satisfy with Highest Stage

  • OFF = Normal staging
  • ON = Y2 or W2 lock
STAGING DELAY Time Between Stages
  • OFF = Temperature based staging (default)
  • 5, 10, 15, 30, 45, 90 minutes
MIN COMP ON Minimum Compressor On Time
  • OFF = No minimum time (default)
  • 3, 4 or 5 minutes
COMP DELAY Minimum Compressor Off Time
  • On = 5 minute delay (default)
  • Off = No delay
COOL FAN DL Cooling Fan Delay Off
  • OFF = No delay (default)
  • 10, 30, 60 or 90 seconds
PROG Programming Option
  • 7d = 7 day schedule
  • 5d = 5 day schedule (default0
  • 0d = No schedule
PRO RECOVERY Early Heating Start
  • ON = On
  • OF = Off
HEAT LIMIT Heating Setpoint Limit
  • 90 deg (default)
COOL LIMIT Cooling Setpoint Limit
  • 44 deg (default)
F OR C SET Temperature Scale
  • F = Fahrenheit (default)
  • C = Celsius
CLOCK SET 12HR or 24HR Clock
  • 12H = 12 hour clock (default)
  • 24H = 24 hour clock
HRDWIRE ONLY Backlight Adjustment