Rheem RPNL / RPQL - Low Pressure - Code L21 - Heating

Rheem Heat Pump: RPNL / RPQL

Re: Heating - Low Pressure Lockout - Code L21

These heat pump models have a control board which monitors equipment operation.

If the low pressure switch trips three times during a run-cycle, a "Hard-Lockout" Code L21 is generated and must be manually reset.

Reset the lockout by 1) Removing Line Voltage Power, 2) Removing Low Voltage Power or 3) Pressing the TEST button for 1 second.


Qty Possible Causes:
1 Low Refrigerant Charge
Bad O/D Expansion Valve

CHECKOUT:

1. Check Equipment Status


2. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

3. Check Defrost


4. Check Air Temperature Rise



Article ID: 764
Last updated: 12 Feb, 2025
Revision: 13
Equipment -> Heat Pumps -> Rheem/Ruud -> RPNL -> Rheem RPNL / RPQL - Low Pressure - Code L21 - Heating
https://ghac.makekb.com/entry/764/