PHE - Defrost Problem / Outdoor Coil Frozen

York Pkg Heat Pump: PHE

Re: Not Defrosting / Outdoor Coil Frozen

The PHE uses a Demand Defrost control board.

The board uses an Ambient (outdoor) Sensor and Liquid Line Sensor to determine the proper conditions for defrost to occur.


Qty Possible Causes:
Bad Liquid Line Sensor
Bad Defrost Board
Bad Condenser Fan Motor
Mis-Placed Coil Sensor
Bad Ambient Sensor
Bad Outdoor Fan
Low Refrigerant Charge
Bad Expansion Valve
Stuck Contactor


CHECKOUT:

1. Check Contactor 


2. Check Outdoor Fan


3. Test Defrost Cycle


4. Check Refrigerant Pressures

DEFROST MODE

Defrost Termination
Refrigerant Suction Pressure Discharge Pressure Liquid Line Temperature
R410A

100-120 Suction

300-375 Discharge

80-90 Deg

HEATING MODE

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

5. Check Liquid Line Sensor


6. Check Ambient Sensor



Article ID: 740
Last updated: 8 Jan, 2024
Revision: 4