Lennox Gas Furnaces: G51MP
Re: Pressure Switch Fault
Diagnostic Light Sequence: DS1 (Red or Green) = Off, DS2 (Green) = Slow Flash
►There are two Differential-Pressure switches wired in series.
A Pressure Switch Fault is caused by one of the following:
- Either Pressure Switch contacts Open with Inducer Energized.
- Both Pressure Switch contacts Closed with Inducer Off.
Qty |
Possible Causes: |
|
Blocked Vent |
1 |
Blocked Intake |
|
Bad Pressure Switch |
|
Bad Inducer Motor |
1 |
Clogged Drain Line or Trap |
|
Item Stuck in Inducer Motor |
|
Bad Ignition Control |
CHECKOUT:
1. Check Furnace Operation
- If the inducer motor is running, de-energize a call for heat by turning the thermostat off, or by removing the control wire from "W" at the furnace board. (Inducer motor should stop after a delay).
- Inducer Motor Continues to Run = Bad Control Board
- Inducer Motor Stops ⇒ Continue
- Start the furnace with a call for heat.
- Inducer motor should start and run.
2. Check Inducer Motor
- With a call for heat, check for 115VAC between the two wires at the plug for the inducer motor.
- Power + No Inducer = Bad Inducer / Capacitor or Blocked Inducer Wheel ⇒ Remove inducer and check wheel.
- No Power = Pressure Switches Stuck Closed or Bad Control Board ⇒ Remove a wire from one of the pressure switches.
3. Check Pressure Switches
- Check for 24VAC between "24V Com" and Pin #1 (HLO) of the 12-pin plug at the furnace control board.
- No Power = No Call for Heat or Bad Control Board
- Check for 24VAC between "24V Com" and Pin #10 (PS) of the 12-pin plug at the furnace control board.
- Power on Pin #1 (HLO) + Power on Pin #10 (PS) + Pressure Switch Fault = Bad Control Board
- Power on Pin #1 (HLO) + No Power Pin #10 (PS) = Open Pressure Switch Circuit ⇒ Check the Switch Contacts (below)
- Switch Contacts
- Check for 24VAC between "24V Com" and both sides of each Pressure Switch.
- Power on Both Sides = Switch Closed
- Power on One Side Only = Open Switch ⇒ Check Switch Pressure (below)
- Switch Pressure
- Unhook both pressure hoses from the open switch.
- Use a pressure gauge to check the differential pressure with the inducer operating. (Trip Point = .85" w.c.)
- Differential Pressure Well Above Trip Point + Open Switch = Bad Pressure Switch
- Differential Pressure Near or Below Trip Point ⇒ Check the inducer and combustion box negative pressures individually.
- High Combustion Box Pressure = Intake/Combustion Air Problem
- Low Inducer Pressure = Vent/Vent Motor Problem or Clogged Drain
- Remove the drain hoses from the plastic drain trap.
- Water pours out of hoses = Clogged Drain or Trap
- Check drain trap for a clog (clean by removing clean-out plugs)