YH2E/YH2F Diagnostic & Fault Codes

York Heat Pump: YH2E / YH2F

Re: Lockout Codes / Fault Codes

The control shall provide fault codes using the Status LED. The table below describes the LED displays during fault codes.

The "lockout" can be Reset by: 1) cycling power to 24V power to the defrost board or 2) turning the thermostat system switch "Off" and then back to "On".


LOCKOUT CODES:

Flashes Description
2 Hi pressure fault (not in lockout yet)
3 Hi pressure lockout (last mode was compressor)
4 Hi pressure lockout (last mode defrost)
5 Low pressure lockout (last mode compressor)
6 Low voltage (< 19.2 volts)
7 Low voltage (< 16 volts)
8 Coil sensor failure (open or shorted)
9 Ambient sensor failure (open or shorted)
10 Control failure
11 "W" and "O" signal received together
12 "Y2" signal present without "Y1"


Article ID: 730
Last updated: 7 Dec, 2023
Revision: 1
Equipment -> Heat Pumps -> York -> YH2E -> YH2E/YH2F Diagnostic & Fault Codes