YZF - High Pressure Faut (Cooling)

York Heat Pump: YZF 

Re: High Pressure Lockout - Last Mode Heat Pump (Cooling)

The heat pump was running in cooling mode and the high pressure switch tripped.

A High Pressure Lockout is indicated by the following LED pattern on the outdoor unit control board:


X/L Output


Qty Possible Causes:
1 Bad Condenser Motor / Capacitor
Refrigerant Over-Charge
Bad I/D Expansion Valve
Low Outdoor Airflow
Refrigerant Restriction
Bad Pressure Switch

CHECKOUT:

1. Check Unit Operation


2. Check O/D Motor & Capacitor


3. Check Refrigerant Pressures

Normal Pressure Range: Cooling
Refrigerant 55-70 Deg O/D 75-100 Deg O/D
R410A
  • 110-130 Suction
  • 250-300 Discharge  
  • 125-150 Suction
  • 270-400 Discharge  

4. Check Sub-Cooling



Article ID: 727
Last updated: 18 Sep, 2023
Revision: 12
Equipment -> Heat Pumps -> York -> YZB / YZF -> YZF - High Pressure Faut (Cooling)