YZF - High Pressure Faut (Cooling)

York Heat Pump: YZF 

Re: High Pressure Lockout - Last Mode Heat Pump (Cooling)

The heat pump was running in cooling mode and the high pressure switch tripped.

High Pressure Lockout is indicated by the following LED pattern on the outdoor unit control board:


X/L Output


Qty Possible Causes:
1 Bad Condenser Motor / Capacitor
Refrigerant Over-Charge
Bad I/D Expansion Valve
Low Outdoor Airflow
Refrigerant Restriction
Bad Pressure Switch

CHECKOUT:

1. Check Unit Operation


2. Check O/D Motor & Capacitor


3. Check Refrigerant Pressures

Normal Pressure Range: Cooling
Refrigerant 55-70 Deg O/D 75-100 Deg O/D
R410A
  • 110-130 Suction
  • 250-300 Discharge  
  • 125-150 Suction
  • 270-400 Discharge  

4. Check Sub-Cooling