Goodman Heat Pump - Defrost Problem / Outdoor Coil Frozen

Goodman Heat Pump: CPLJ

Re: Won't Defrost

The Goodman CPLJ Heat Pump uses a Time & Temperature Defrost Board.


Qty Possible Causes:
1 Bad or Disconnected Defrost Stat
Bad Defrost Board
Stuck Contactor
Low Refrigerant Charge
Bad Cond Fan Motor / Capacitor
Mis-Located Defrost Stat
Stuck Reversing Valve
Defrost Timer Set Too Long

CHECKOUT:

1. Check Operating Status


2. Check Fan Motor


3. Check Refrigerant Charge

Hook-up refrigerant gauges to the pressure ports on the unit.

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R-22
  • 20-40 Suction
  • 150-225 Discharge
  • 40-75 Suction
  • 170-260 Discharge

4. Check Defrost Board