York Heat Pumps: YHJF
Re: Indoor & Outdoor Running Continuous
Even with the thermostat in the "Off" position, both the outdoor unit and indoor unit continue to run.
► The blower and auxiliary heaters are typically working normally or the customer would also be experiencing no heat.
Qty |
Possible Causes: |
2 |
Stuck Contactor |
|
Shorted Wiring |
|
Bad Thermostat |
|
Mis-Wired Low Voltage |
CHECKOUT:
1. Check Outdoor Low Voltage
- Open the electrical compartment cover at the outdoor unit.
- Check for 24VAC across the compressor contact coil.
- No 24VAC Power + Outdoor Unit Running = Stuck Contactor (Indoor unit is probably running due to multiple limit trips)
- 24VAC Power Present ⇒ Check for 24VAC between "Y" and "C" on the stat wire connections.
- No 24VAC Power + Power at the Contactor = "That's really weird! Call Will P."
- 24VAC Present on "Y" → Step 2. Check Thermostat
2. Check Thermostat
- Remove the thermostat from the sub-base and check to see if the outdoor unit shuts off.
- Outdoor Unit Shuts Off = Bad Thermostat
- Outdoor Unit Continues to Run ⇒ At the sub-base, remove the "Y" wire and re-check to see if the outdoor unit goes off.
- Outdoor Unit Goes Off = Bad Sub-Base (Replace Thermostat and Sub-Base)
- Outdoor Unit Continues to Run ⇒ Check for 24VAC between the "Y" wire and "C".
3. Check Wiring
- At the air handler, open the blower door and inspect the low voltage wiring.
- Look for any wiring damage or or jumpers left in-place.
- Make sure the Condensate Overflow Switch is wired correctly.