M4PG4 - Flashing Code 4

Ameristar Package Unit: M4PG4

Re: Flashing Code 4

Code 4 = Main Limit switch or Aux Limit (not a Roll-Out Limit) has opened its normally closed contacts.

► The manual-reset Aux Limit is located in the blower compartment.

 The automatic-reset Main Limit Switch is located in the main burner compartment.


Main Limit Switch Aux Limit Switch
Qty Possible Causes: Qty Possible Causes:
Dirty or Restrictive Air Filter 1 Bad Blower Motor
Clogged Evaporator Coil No Air Circulation
High Duct Static Power Failure
2 High Gas Pressure Bad Limit Switch
1 Bad Limit
1 Blower Speed too Low


CHECKOUT:

1. Check Limits


2. Check Temperature Rise


3. Check Air Filter


4. Check Gas Pressure


5. Check Blower Motor & Blower Speed


6. Check Duct Static Pressure