YZE/YZF - High Pressure (Defrost)

York Heat Pump: YZE/YZF

Re: High Pressure Fault (Defrost)

The heat pump was running in defrost mode and the high pressure switch tripped.

A Defrost High Pressure Lockout is indicated by the following LED pattern on the outdoor unit control board:


Qty Possible Causes:
1 Bad Liquid Line Sensor
2 Refrigerant Over-Charge
Refrigerant Restriction
Bad Pressure Switch


CHECKOUT:

1. Check Liquid Line Sensor


2. Check Indoor Airflow


3. Check Blower Motor


4. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

5. Check Sub-Cooling


6. Check Indoor Airflow


7. Check Duct Static Pressure



Article ID: 694
Last updated: 22 Nov, 2021
Revision: 3