WHITE-RODGERS FURNACE CONTROL - LOCKOUT CODES
When system lockout occurs, the gas valve is de-energized, the circulator blower is energized at HEAT speed, and, if flame is sensed, the inducer blower is energized. The diagnostic indicator light will flash or glow continuously to indicate system status.
50A55 & 50M56 Integrated Furnace Control
Code | Description |
1 | System lockout due to failed ignition attempts |
2 | Pressure switch stuck closed |
3 | Pressure switch stuck open |
4 | Open limit switch |
5 | Flame sensed with gas valve de-energized |
6 | Open rollout (or blown fuse) |
7 | Low flame sense signal |
8 | Igniter relay fault |
Rapid | Reversed polarity |
On | Normal operation |
Off | No power or bad control |
50A50-206 Integrated Furnace Control
Code | Description |
On | Replace control |
1 | Lockout due to failed ignition |
2 | Pressure switch stuck closed |
3 | Pressure switch stuck open |
4 | Open limit |
5 | Missing jumper wire |
Rapid | Flame sensed with no call for heat |
50A50-241 & 50A51-243 Integrated Furnace Control
Code | Description |
On | Replace Control |
2 | Pressure switch stuck closed |
3 | Pressure switch stuck open |
4 | Open limit switch |
5 | Open rollout switch |
6 | Lockout caused by pressure switch |
7 | Lockout caused by no ignition |
8 | Lockout caused by loss of flame |
Rapid | Flame sensed with no call for heat |
Off | No power or bad control |
To Reset the control after a lockout, do one of the following:
Non-Integrated Furnace Control
Code | Description |
Green On | Normal Operation |
Green Flashing | Weak flame signal |
Yellow On | Internal Self-Check |
Yellow Flashing | Improper Polarity |
Red On | Replace Control |
Red Flashing | Lockout |