RHA - Defrost Problem / Outdoor Coil Frozen

Amana Heat Pump: RHA

Re: Defrost Problem / Outdoor Coil Frozen

The Amana RHA Heat Pump uses a Time & Temperature Defrost Board.


Qty Possible Causes:
Bad Defrost Stat
1 Bad Defrost Board
Low Refrigerant Charge
Bad Cond Fan Motor / Capacitor
Stuck Reversing Valve
Defrost Timer Set Too Long

CHECKOUT:

1. Check Operating Status


2. Check Fan Motor


3. Check Defrost


4. Check Refrigerant Charge

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R-22
  • 20-40 Suction
  • 150-225 Discharge
  • 40-75 Suction
  • 170-260 Discharge