GSV/GSH - Flashing Code 2 (Heating)

Climatemaster Geothermal: GSV/GSH

Re: Code 2 / High Pressure Fault (Heating)

Code 2 = High Pressure Fault

► There may be an optional High Water Temperature Switch (HWTS) or a High Water Pressure Switches (HWPS) wired in series with the refrigerant High Pressure Switch.

► When the high pressure switch circuit opens the compressor relay is de-energized immediately since the high pressure switch is in series with the compressor contactor coil.


Qty Possible Causes:
Refrigerant Over-Charge
Low Airflow
1 Bad Blower Motor / Capacitor
Bad Blower Relay
Bad Expansion Valve
Bad Pressure Switch


CHECKOUT:

1. Check Indoor Airflow


2. Check Blower Motor


3. Check Operating Conditions

► Be sure to re-connect the 3-wire heater plug and HWG pump before closing the unit.


4. Check Air Filter & Indoor Coil


5. Check Duct Static Pressure



Article ID: 651
Last updated: 8 Feb, 2023
Revision: 8
Equipment -> GeoThermal -> Climatemaster -> GSV/GSH -> Diagnostics -> GSV/GSH - Flashing Code 2 (Heating)