AHX/MX Air Handler - Fan Runs Continuous - No Faults

York Air Handler: AHX/MX

Re: Fan Running Continuous - No Fault Codes

The customer reports that the indoor blower runs continuous.

► This is normally associated with a Code 3 on the air handler board, but in this case there is no fault indication on the board.


Qty Possible Causes:
Bad Control Board
2 Bad X-13 Blower Motor
Thermostat set to fan "On"
Shorted Low Voltage Wiring
Bad Thermostat/Subbase

Checkout:

1. Check the Thermostat


2. Check Low Voltage


3. Check Control Board