Goodman GPG13 - Flashing Code 4

Goodman Package Unit: GPG13

Re: Flashing Code 4

If the limit control opens, the burners will be de-energized and the air circulation and vent blower will be powered until the limit closes.

The diagnostic light code for this is four short flashes followed by a pause.

The diagnostic code will go away and operation will resume once the limit switch closes.


Qty Possible Causes:
Dirty or Restrictive Air Filter
Clogged Evaporator Coil
Bad Blower Motor/Capacitor
2 Bad Control Board
Under-sized Ductwork
High Gas Pressure
Bad Limit
Blower Speed Too Low


CHECKOUT:

1. Check Control Board / Limit Circuit


1. Check Blower Operation


2. Check Temperature Rise


3. Check Air Filter


4. Check Gas Pressure


5. Check Duct Static Pressure


6. Check Blower Motor/Blower Speed



Article ID: 631
Last updated: 24 Dec, 2022
Revision: 4
Equipment -> Package Units -> Goodman -> GPG13 -> Goodman GPG13 - Flashing Code 4