York 90% Gas Furnace: P*MPD
Re: Flashing Code 3
Code 3 = Furnace Pressure Switch failed to close on a call for heat.
This gas furnace has a single pressure switch which monitors for proper venting.
Qty |
Possible Causes: |
1 |
Bad Inducer Motor |
1 |
Bad Pressure Switch |
|
Clogged Pressure Port |
|
Bad Vent Blower Wheel |
|
Blocked Vent |
|
Item Stuck in Inducer Motor |
CHECKOUT:
1. Check Control Board
- Start the furnace with a call for heat.
- The Inducer motor should start within 15 seconds.
2. Check Inducer Motor
- Start the furnace with a call for heat.
- Observe and listen to the inducer motor.
- Inducer motor hums but does not start:
- Bad Inducer Motor or Capacitor
- Item in Inducer ⇒ Remove inducer & check
- Inducer motor does not attempt to start & shows Code 3 ⇒ Check for 115V power to inducer.
- Power + No Inducer = Bad inducer Motor
- No Power = Bad Control Board
3. Check Pressure Switch
- Ensure the pressure switch hose is properly attached at both ends.
- Switch Contacts
- With the wires attached to the switch, check for 24VAC between each terminal of the switch and Common.
- 24VAC On One Side Only = Open Switch ⇒ Use a pressure meter to check the Switch Pressure (below).
- 24VAC On Both Sides = Switch Closed
- Switch Closed + Code 3 ⇒ Check Power at the control board plug
- Switch Pressure
- Remove the pressure hose from the Inducer Motor.
- Connect a pressure meter to the Inducer Motor pressure port.
- Compare actual pressure to the pressure rating on the switch.
- Pressure Near or Below Rating = Clogged or Restricted Vent or Bad Vent Blower Wheel ⇒ Remove and Check Blower
- Pressure Well Above the Rating + Open Switch = Bad Switch