The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.


DIAGNOSTIC CODES:

Green Red Description
Off Off No Power to Control
Simultaneous Slow Normal Operation
Alternating Slow Anti-Short Cycle Delay
Off Slow Low Pressure Fault
Off On low Pressure Lockout (5 trips)
Slow Off High Pressure Fault
On Off High Pressure Lockout (5 trips)