YHE/YHG - Code 3 - High Pressure - Heating

York YHE / YHG Heat Pump: Heating

Re: High Pressure Fault - Last Mode Heat Pump

The heat pump was running in normal heat mode (not in defrost) and the high pressure switch tripped.

High Pressure Lockout is indicated by a 3-Flash LED pattern on the outdoor unit control board.


X/L Output


Qty Possible Causes:
1 Refrigerant OverCharge
  Bad O/D Expansion Valve
Bad Blower Motor / Capacitor
Low Indoor Airflow
Refrigerant Restriction
Bad Pressure Switch


CHECKOUT:

1. Check Indoor Airflow


2. Check Blower Motor


3. Check Refrigerant Pressures


4. Check Sub-Cooling


5. Check Heat Pump Temperature Rise


6. Check Indoor Airflow


7. Check Duct Static Pressure



Article ID: 596
Last updated: 29 Dec, 2021
Revision: 8
Equipment -> Heat Pumps -> York -> YHE -> YHE/YHG - Code 3 - High Pressure - Heating
https://ghac.makekb.com/entry/596/