York Rooftop Unit: DH, DM
Re: Flashing Code 8
Flashing Code 8 = Compressor 2 Freezestat open.
If there is a call for Y2 and the FP2 input is open, the control will lockout stage 2 compressor and flash a code 8.
Qty |
Possible Causes: |
1 |
Bad Freezestat |
1 |
Broken or Loose Blower Belt |
|
Dirty Air Filters or Coil |
|
Bad Fan Contactor |
|
Bad Control Board |
CHECKOUT:
1. Check Freezestat
- Remove the 6-wire (4-Black, 2-Blue) Plug from the control board.
- Check resistance across the two lower black wires.
- Resistance = Freezestat OK
- No Resistance = Freezestat Open
2. Check Blower Operation
- Start the unit with a call for Fan.
- Place a jumper wire between "R" and "G" if the thermostat is not already calling for Fan.
- The fan contactor should energize immediately.
3. Check Fan Contactor
- Check for 24VAC across the Fan Contactor coil.
- No Power = Bad Control Board
- Power Present + Not Engaged = Bad Fan Contactor
- Check for 230VAC across the inlet and outlet sides of the contactor.
- Power In + No Power Out = Bad Fan Contactor
4. Check Blower
- Open the blower access panel and check blower operation and belt/belt tension.
- No Blower Operation ⇒ Turn off power to the unit and check the motor for burnt wiring or open windings.
5. Check Filters/Coil
- Open the side compressor access panel and check the air filters and evaporator coil.
Article ID: 558
Last updated: 14 Dec, 2018
Revision: 4
Equipment -> Rooftop Units -> York -> Predator DH, DM, -> Predator - Flashing Code 8