Predator - Flashing Code 7

York Rooftop Unit: DH, DM

Re: Flashing Code 7

Flashing Code 7 = Compressor 1 Freezestat open.


If there is a call for Y1 and the FP1 input is open, the control will lockout stage 1 compressor and flash a code 7.


Qty Possible Causes:
1 Bad Freezestat
Broken or Loose Blower Belt
Dirty Air Filters or Coil
Bad Fan Contactor
Bad Control Board


CHECKOUT:

1. Check Freezestat


2. Check Blower Operation


3. Check Fan Contactor


4. Check Blower


5. Check Filters/Coil



Article ID: 557
Last updated: 14 Dec, 2018
Revision: 5
Equipment -> Rooftop Units -> York -> Predator DH, DM, -> Predator - Flashing Code 7
https://ghac.makekb.com/entry/557/