ClimateMaster Heat Pump: TEV
Re: Code 10/ECM Blower Fault
When operating an ECM blower, there are two types of ECM Blower fault conditions that may be detected:
- An ECM blower fault will be detected and the control will lockout after 15 seconds of blower operation with the blower feedback signal reading less than 100 RPM.
- An ECM blower fault will be detected when the ECM configuration is incorrect or incomplete. For this fault condition, the control will continue to operate using default operating parameters.
Qty |
Possible Causes: |
|
Bad ECM Blower Motor |
|
Incorrect Configuration |
|
|
CHECKOUT:
1. Check Configuration
- If available, connect a Climatemaster communicating thermostat to the unit.
- From the Home Screen, go into Service Mode by holding the Up & Down arrows for 5 seconds.