GCV/GSH - Flashing Code 5 (Cooling)

ClimateMaster Heat Pump: GSV/GSH

Re: Flashing Code 5 / LT2 Fault (Cooling)

Code 5 = Low Air Coil Temperature (FP2)


Qty Possible Causes:
3 Low Refrigerant Charge
1 Expansion Valve Underfeeding
Bad FP2 Sensor
Low Air Flow (Filter or Coil)
Low Air Flow (Fan Speed)

CHECKOUT:

1. Check Operating Conditions

► Be sure to re-connect the HWG pump before closing the unit.


2. Compare to Unit Performance Chart


3. Check FP2 Sensor



Article ID: 554
Last updated: 8 Feb, 2023
Revision: 4
Equipment -> GeoThermal -> Climatemaster -> GSV/GSH -> Diagnostics -> GCV/GSH - Flashing Code 5 (Cooling)