Mammoth Heat Pump: D013
Re: Error Code 1 / Fault Code 1 - Cooling
Code 1 = High Pressure Switch Fault
Qty |
Possible Causes: |
|
Refrigerant Over-Charge |
|
Bad Expansion Valve |
1 |
Low Water Flow |
|
Bad Pressure Switch |
CHECKOUT
1. Check Refrigerant Pressures
- Hook-up refrigerant gauges to the system.
- Start unit and monitor pressures.
- Normal R-22 Pressures = 55 - 75 Suction, 200 - 275 Discharge.
- Normal R410A Pressures = 100 - 150 Suction, 275 - 400 Discharge.
- Check temperature rise on the water lines at the unit.
- Normal water temperature rise = 9-15 deg.
- High Head Pressure & Normal Temperature Rise = Refrigerant Overcharge
- High Head Pressure & High Temperature Rise = Low Water Flow
2. Check Pressure Switch
- If refrigerant discharge pressure stays in a normal range but still shows Code 1 ⇒ Check Pressure Switch
- Without removing wires, check for 2VAC on both sides of the pressure switch.
- Power on Both Sides = Switch Closed
- Power on One Side Only = Switch Open (Bad Switch)