PGB - Flashing Code 4

Amana Package Unit: PGB

Re: Flashing Code 4

Code 4 = Open Limit Circuit

There are three limits in the limit circuit:

► If the Primary Limit trips 5 times during a single call for heat, the control will enter a Lockout and flash Code 8.


Qty Possible Causes:
Dirty Filter
Bad Blower Motor
High Gas Pressure
High Duct Static
Blower Speed Too Low
Bad Limit
Tripped Roll-Out (Heat Exchanger)


CHECKOUT:

1. Check Limit Circuit


2. Check Blower Operation


3. Check Temperature Rise


4. Check Air Filter


5. Check Gas Pressure


6. Check Duct Static/Blower Speed



Article ID: 530
Last updated: 18 Apr, 2018
Revision: 6
Equipment -> Package Units -> Amana -> PGB -> PGB - Flashing Code 4
https://ghac.makekb.com/entry/530/