YHJF24 - YHJF48 Heat Pump Wiring Diagram

THERMOSTAT: This application uses a Honeywell VisionPro Thermostat to control a 2-stage heat, 1-stage cool Heat Pump.


SCHEDULE: The VisionPro thermostat is pre-configured as Programmable and has a default schedule with all temperatures set for 68 deg. Heat, 74 deg. Cool. However, the thermostat has the option to be Programmable or Non-Programmable.

To change the Schedule Options:


WIRING: There are several important points to watch for on the wiring.

  1. The "Y" wire from the thermostat must connect to "Y/Y2" at the air handler (not Y1), otherwise the indoor blower will operate on the Low Fan speed with compressor operation.
  2. The Condensate Overflow Switch must be wired as-shown to break the "Y" signal to the outdoor unit.

FAN SPEEDS: Fan speed selection on the air handler is very important since we are using an oversized blower.


HUMIDIFIER: The thermostat is pre-configured to control a Bypass Humidifier (if applicable).