York Heat Pump: YZE/YZH
Re: Not Defrosting / Outdoor Coil Frozen
These units use a Yorkguard VI Demand Defrost control board.
The board uses an Ambient (outdoor) Sensor and Liquid Line Sensor to determine the proper conditions for defrost to occur.
	
		
			| Qty | 
			Possible Causes: | 
		
		
			 | 
			Bad Liquid Line Sensor | 
		
		
			|  1 | 
			Bad Condenser Fan Motor | 
		
		
			 | 
			Bad Fan Capacitor | 
		
		
			|   | 
			Bad Defrost Board | 
		
		
			 | 
			Mis-Located Sensor | 
		
		
			 | 
			Low Refrigerant Charge | 
		
		
			 | 
			Bad Expansion Valve | 
		
	
CHECKOUT:
1. Check Outdoor Fan
	- Make sure the thermostat is calling for heat and the heat pump is not currently in a Lockout Fault.
 
	- Inspect the outdoor unit and make sure the outdoor fan is operating.
	
		- Fan Operating → Step 2. Test Defrost Cycle
 
		- No Fan ⇒ 
		
			- PSC Models - Check for 230VAC to the fan motor between the  Purple  and  Black  wires.
			
				- No Power = Bad Control Board or Unit in Defrost
 
				- Power + No Fan Operation = Bad Fan Motor or Capacitor ⇒ Check Capacitor
 
			
			 
			- V/S Models - Check for 24VAC between  Blue  at the compressor contactor low voltage coil &  Yellow  at the Yorkguard "ODF" terminal.
			
				- No Power = Bad Control Board or Unit in Defrost
 
				- Power + No Fan Operation = Bad Fan Motor/Controller
 
			
			 
		
		 
	
	 
2. Check Defrost
	- Yorkguard VI
 
	- Jump the two "TEST" pins on the outdoor unit control board.
	
		- If the outdoor (ambient) temperature is below 50 deg. and above -25 deg. the unit should enter a defrost mode.
 
	
	 
	- Ensure that the outdoor fan shuts-off and the reversing valve switches to cooling mode.
	
		- The unit should exit defrost when the liquid line temperature reaches 80 deg.
		
		
 
	
	 
3. Check Liquid Line Sensor
	- Disconnect high voltage power from the unit by pulling the service disconnect or turning the breaker off.
 
	- Disconnect low voltage from the defrost board by removing the  Red , "R" wire.
 
	- Sensor Resistance
 
	- Disconnect the two  Blue  wires from the defrost board connected to "LL" and "LLG".
 
	- Set the multi-meter on 200K (not 200) Ohms.
 
	- Test resistance of the sensor.
 
	- Use Resistance Chart to determine sensed temperature.
	
		- If sensed temperature is more than 5 deg. higher or lower than the actual temperature = Bad Liquid Line Sensor
 
	
	 
	- Sensor Location
 
	- It is very common for technicians to put the liquid line sensor in the wrong location (which can cause the unit to terminate defrost before the coil is thawed).
 
	- The sensor must be located on the condenser (outdoor) coil side of the metering device, as close to the metering device as possible.
	
		- With an expansion valve, it is possible to mount the sensor between the valve and the coil distributor.
 
		- With an orifice, the proper location is typically where one of the distributor lines ties into a short 3/8" piece of copper at the coil.
 
	
	 
4. Check Ambient Sensor
	- Disconnect high voltage power from the unit by pulling the service disconnect or turning the breaker off.
 
	- Disconnect low voltage from the defrost board by removing the  Red , "R" wire.
 
	- Disconnect the two  White  wires from the defrost board connected to "AMB" and "AMBG".
 
	- Set the multi-meter on 200K (not 200) Ohms.
 
	- Test resistance of the sensor.
 
	- Use Resistance Chart to determine sensed temperature.
	
		- If sensed temperature is more than 5 deg. higher or lower than the actual temperature = Bad Ambient Sensor
		
			- Ambient Temperature reading less than 50 deg and the board will not initiate defrost = Bad Defrost Board
 
		
		 
	
	 
5. Check Refrigerant Pressures
	- Hook-up refrigerant gauges to the pressure ports on the unit.
	
		- Blue --> "True Suction" Port (Not the Suction Line)
 
		- Red --> High Pressure (either refrigerant line)
 
	
	 
	- Monitor pressures as the system operates.
 
	- DO NOT ATTEMP TO ADJUST REFRIGERANT CHARGE WHILE THE COIL IS FROZEN!
 
	
		
			| Normal Pressure Range | 
		
		
			| Refrigerant | 
			0-30 Deg O/D | 
			30-50 Deg O/D | 
		
		
			| R410A | 
			
			
				- 75-100 Suction
 
				- 250-320 Discharge
 
			 
			 | 
			
			
				- 100-150 Suction
 
				- 250-375 Discharge
 
			 
			 | 
		
	
	- If a Liquid-Line Sight Glass is installed, observe for bubbles in the sight glass (after the system has been operating for at least 5 min.)
	
		- Bubbles = Low Refrigerant Charge
 
	
	 
	- Low Pressure Issues
	
		- Low Suction + Low Discharge + Bubbles in Sight Glass + O/D Expansion Valve Frosting = Low Refrigerant Charge
		
			- Try adding refrigerant through the Low Pressure gauge.
			
				- Suction and Discharge Pressures should gradually increase as refrigerant is added.
 
				- If the Discharge Pressure increases but the Suction stays low or drops = Bad O/D Expansion Valve
 
			
			 
		
		 
		- Low Suction + Clear Sight Glass + Expansion Valve Frosting = Bad O/D Expansion Valve