Yorkguard VI - Aux Heat Stuck On

York Heat Pump: YorkGuard VI

Re: Aux Heat Stuck On

The auxiliary heaters stick on and the customer reports overheating of the controlled space.

The Yorkguard VI board controls Aux Heat operation through the W1-Out and W2-Out terminals.

Balance Point

If the outdoor ambient temperature is less than the Balance Point setting and above LTCO and a W input is received with a Y1 input, the control will energize the compressor contactor output based on the Y1 input and will energize the W1-Out immediately when the W input is received.

When the W input is received, the control will start a fifteen-minute timer. If the call for Y1 + W is still present after the fifteen-minute timer expires, the control will then energize W2-Out along with W1-Out. 

LTCO

If the outdoor ambient temperature is below the LTCO setting, the control will de-energize the compressor and energize W1-Out immediately when a Y1 input is received. W2-Out will act as 2nd stage heat and be energized on a call for W.

Defrost

The control will energize W1-Out 30 second prior to and during defrost operation. If W1-Out has been energized for 15 minutes W2-Out will be energized also. The W1-Out and W2-Out will remain energized (depending on the 15 minute timer) 180 seconds after the defrost cycle has been terminated. 


Qty Possible Causes:
2 Mis-Wired Low Voltage
Bad Heat Relay
Low Voltage Short
Bad YorkGuard Module


CHECKOUT:

1. Check Thermostat


2. Check Heaters


3. Check Yorkguard


4. Check Low Voltage Wiring

Stat A/H H/P
R R R
C C C
O O O
G G -
W - W
Y1 Y1 Y1
Y2 - Y2
- W1 W1 OUT
W2 W2 OUT
Y2 Y2 OUT
L - X/L

► Placing a jumper between "W" and "W1-OUT" or "W2-OUT" (at the air handler or heat pump) WILL CAUSE THE AUX HT TO STICK ON!



Article ID: 489
Last updated: 22 Jan, 2018
Revision: 6
Equipment -> Heat Pumps -> York -> YZE/YZH -> Yorkguard VI - Aux Heat Stuck On