Yorkguard - Flashing Code 5

York Heat Pump: EFH

Re: Flashing Code 5

Code 5 - Defrost Fault (Going into defrost too often).

These units use a Yorkguard Demand Defrost control board. The board uses an Ambient (outdoor) Sensor and Liquid Line Sensor to determine the proper conditions for defrost to occur.

► If the board senses that the coil temperature sensor is getting too cold, too quickly, and requiring defrost too often - a Code 5 is generated.


Qty Possible Causes:
1 Bad Liquid Line Sensor
 1 Bad Condenser Fan Motor
Bad Fan Capacitor
  Bad Defrost Board
1 Mis-Located Sensor
Low Refrigerant Charge
Bad Expansion Valve


CHECKOUT:

1. Check Outdoor Fan


2. Check Defrost


3. Check Liquid Line Sensor


4. Check Ambient Sensor


5. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R-22
  • 20-45 Suction
  • 175-225 Discharge
  • 40-55 Suction
  • 180-250 Discharge


Article ID: 488
Last updated: 6 Feb, 2023
Revision: 6
Equipment -> Heat Pumps -> York -> EFH -> Yorkguard - Flashing Code 5