TM9Y - Flashing Code 3

York Gas Furnace: TM9Y

Re: Flashing Code 3

Code 3 = The normally open (PS1 or PS3) pressure switch contact did not close after the inducer was energized.

► This is a "Soft Lockout" which will automatically reset after 1 hour.

► There are 3 pressure switches on this furnace. PS1 (1st Stage Switch usually .90") and PS3 (Condensate Switch usually .20") are wired in series to the pressure switch input. 

► The PS2 (2nd Stage Switch) wires in separately and will cause a Code 13.


Qty Possible Causes:
1 Bad Inducer Motor
Water in Vent
1 Water in Inducer/Clogged Drain
2 Improper Condensate Drainage
Clogged or Restricted Vent
Bad Pressure Switch
Water in Pressure Switch / Tubing


CHECKOUT:

1. Check Inducer Motor Operation


2. Check Pressure Switches


3. Check Condensate Drainage



Article ID: 472
Last updated: 19 Feb, 2024
Revision: 9
Equipment -> Gas Furnaces -> York -> TM9Y -> TM9Y - Flashing Code 3