Climatemaster Diagnostic Codes

Geothermal Heat Pump: Climatemaster

Re: Diagnostic Codes

CXM Board - Most older Climatemaster Geothermal heat pumps use the CXM Control Board.


DIAGNOSTIC CODES:
Flashing Description
1 No faults in memory
2 High pressure fault
3 Low pressure fault
4 Water coil freeze-protect (heating)
5 Air coil freeze protect (cooling)
6 Condensate overflow fault
7 Over/Under voltage fault (<18 or >31.5 VAC)
8 Unit Performance Sentinel
9 FP1 & FP2 Swapped

FAULT DESCRIPTION:


WHAT TO CHECK:

Code Cooling Heating
2
  • Low water pressure
  • Low water flow
  • Water too hot
  • Bad circulating pump
  • Low airflow
  • Bad blower motor
  • Clogged air filter
  • Dirty indoor coil
  • Overcharged
3
  • Low refrigerant charge
  • Bad expansion valve
  • Bad switch
  • Low refrigerant charge
  • Bad expansion valve
  • Bad switch
4
  • N/A
  • JW3 not clipped
  • Low refrigerant charge
  • Low water flow
  • Bad circulating pump
  • Bad expansion valve
  • Bad sensor
5
  • Low refrigerant charge
  • Low airflow
  • Bad blower motor
  • Bad expansion valve
  • Bad sensor
  • N/A
6
  • Clogged drain hose
  • Clogged drain line
  • Double trapped
  • Shorted CO sensor
  • N/A
7
  • Transformer mis-wired
  • Low line voltage
  • Transformer mis-wired
  • Low line voltage
8
  • Low refrigerant
  • Low airflow
  • Bad expansion valve
  • Bad sensor
  • Low refrigerant
  • Low water flow
  • Bad expansion valve
  • Bad sensor
9
  • Swapped sensors
  • Bad sensor(s)
  • Swapped sensors
  • Bad sensor(s)



Article ID: 46
Last updated: 6 Apr, 2017
Revision: 12
Equipment -> GeoThermal -> Climatemaster -> TS/TT -> Diagnostics -> Climatemaster Diagnostic Codes