Lennox Rooftop Unit: TGA
Re: Heating Diagnostic/Fault Codes
LED Flashes | Description |
Slow Continuous | Normal - No Call for Heat |
Fast Continuous | Normal - Call for Heat |
Off | Internal Fault or No Power |
On | Control Failure |
2 Flashes | Failed Ignition or Flame Loss |
3 Flashes | Roll-out Open or Pressure Switch Fault |
4 Flashes | Limit Open or Limit Open 3 Times |
5 Flashes | Flame Sensed with Gas Valve Off |