4TWX8 - Kicking On & Off (Heating)

Trane Heat Pump: 4TWX8

Re: Compressor Kicks On and Off (Heating)

The compressor and condenser fan motor cycle on and off rapidly.

►The 4TWX8 models have a 2-Stage Scroll compressor.

►The 4TWX8 models uses an Electronic Expansion Valve (EEV) for superheat control.

► The High Pressure switches is wired in series with the "Yo" output from the defrost board to the compressor contactor and the Low Pressure is wired in series with Common (B).  A tripped LPCO or HPCO switch will de-energize the contactor when it opens and re-energize once the switch closes. (No lockout).


Qty Possible Causes:
High Pressure - Overcharged
Low Pressure - Low Refrigerant Charge
High Pressure - Low Indoor Airflow
Low Pressure - Bad Electronic Expansion Valve
Low Pressure - Bad Suction Sensor
1 Low Pressure - Bad Pressure Transducer

CHECKOUT:

1. Check Fault Codes


2. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 40-85 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

2. Check High Pressure Issues


3. Check Low Pressure Issues