EFH - Not Defrosting / Outdoor Coil Frozen

York Heat Pump: EFH

Re: Not Defrosting / Outdoor Coil Frozen

These units use a Yorkguard Demand Defrost control board.

The board uses an Ambient (outdoor) Sensor and Liquid Line Sensor to determine the proper conditions for defrost to occur.


Qty Possible Causes:
1 Bad Liquid Line Sensor
  Bad Condenser Fan Motor
Bad Fan Capacitor
  Bad Defrost Board
1 Mis-Located Sensor
Low Refrigerant Charge
Bad Expansion Valve


CHECKOUT:

1. Check Outdoor Fan


2. Check Defrost


3. Check Liquid Line Sensor


4. Check Ambient Sensor


5. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R-22
  • 20-45 Suction
  • 175-225 Discharge
  • 40-55 Suction
  • 180-250 Discharge



Article ID: 446
Last updated: 6 Feb, 2023
Revision: 8
Equipment -> Heat Pumps -> York -> EFH -> EFH - Not Defrosting / Outdoor Coil Frozen