Trane Gas Furnace: TUD
Re: Flashing Code 7
Code 7 = Gas Valve Circuit Error
	
		
			| Qty | Possible Causes: | 
		
			|  | Bad Control Board | 
		
			| 1 | Bad Gas Valve | 
		
			|  | Bad Wiring | 
	
CHECKOUT:
1. Check Gas Valve
	- Disconnect line voltage power to the furnace.
- Unhook the 3-wire plug at the gas valve.
- Check the resistance of the gas valve coil windings ("C" to "PM").
	
		- Windings Open = Bad Gas Valve
- Windings Show Resistance ⇒ 
		
			- Re-attach the 3-wire plug at the gas valve.
- Unplug the 12-Pin plug from the ignition control board.
- Check resistance between Pins 7 (RD/I) and 8 (BL/I).
			
				- No Resistance = Bad Wiring between Gas Valve & Ignition Control Board.
 
 
 
2. Check Control Board
	- Re-attach the 12-Pin plug to the Ignition Control Board.
- Re-attach the 3-Pin plug to the gas valve (if loose).
- Re-apply power to the furnace.
- Energize a call for heat.
	
		- Still Flashes Code 7 = Bad Control Board