DNZ - Flashing Code 8

Package Unit: DNZ

Re: Flashing Code 8

These units have one control board (EMCB) which controls all unit functions.

► Any heating diagnostics will be displayed on the EMCB.

CODE 8 = Flame sensed with gas valve OFF. 

If flame is sensed for longer than 4.0 seconds during a period when the gas valve should be closed, the control will enter lockout, flashing the LED 8 times.

The control will turn on the inducer and blower motor while the flame is sensed.


Qty Possible Causes:
1 Bad Control Board
Sticking Gas Valve
Shorted Flame Sensor

CHECKOUT:

1. Check Flame Sensor


2. Check the Gas Valve