4TWR3 - Defrost Problem / Outdoor Coil Frozen

Trane Heat Pump: 4TWR3

Re: Not Defrosting / Frozen

The 4TWR3 models use a Demand Defrost control board.

The board uses an Ambient (outdoor) Sensor and Liquid Line Sensor to determine the proper conditions for defrost to occur.


Qty Possible Causes:
Bad Liquid Line Sensor
Bad Condenser Fan Motor
Bad Fan Capacitor
1 Bad Defrost Board
Low Refrigerant Charge
Bad Expansion Valve
No 24VAC Power


CHECKOUT:

1. Check Outdoor Fan


2. Test Defrost Cycle


3. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

4. Check Liquid Line Sensor


5. Check Ambient Sensor


6. Defrost Termination Temperature