GSV/GSH - Flashing Code 3

Climatemaster Geothermal: GSV/GSH

Re: Flashing Code 3 / Loss of Charge

Code 3 = Low Pressure Fault

The low pressure switch must be open and remain open for 30 continuous seconds during an “on” cycle to be recognized as a low pressure fault.

If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a low pressure (loss of charge) fault.


Qty Possible Causes:
2 Low Refrigerant Charge
Bad Expansion Valve
Bad Pressure Switch


CHECKOUT:

1. Check Standing Pressure


2. Check Operation


3. Check Operating Pressures



Article ID: 433
Last updated: 8 Feb, 2023
Revision: 6
Equipment -> GeoThermal -> Climatemaster -> GSV/GSH -> Diagnostics -> GSV/GSH - Flashing Code 3