Trane Package Unit: 4YCC4
Re: Flashing Code 4
Code 4 = High Limit or Roll-Out Switch Open
* After 4 limit trips during a single call for heat, the control will enter a 1-Hour Soft Lockout and flash Code 4.
Qty |
Possible Causes: |
|
Dirty Filter |
|
Bad Blower Motor |
1 |
High Gas Pressure |
2 |
High Duct Static |
|
Blower Speed Too Low |
|
Bad Limit |
2 |
Tripped Roll-Out |
CHECKOUT:
1. Check Limit Circuit
- Primary Limit (located behind the blower housing)
- On the ignition control board, check for 24VAC between PP-9 >> 37A (OR) and Gnd.
- Check for 24VAC between PP-8 >> 39A (OR) and Gnd.
- Power on Both = Primary Limit Closed ⇒ Check Roll-Out Limit
- Power on One Only = Primary Limit Open
- Roll-Out Limit (located on the right-hand side of the burner manifold)
- Check for 24VAC between PP-8 >> 38A (OR) and Gnd.
- Check for 24VAC between PP-6 >> 49A (PR) and Gnd.
- Power on Both = Roll-Out Limit Closed → Step 2. Check Temperature Rise
- Power on One Only = Roll-Out Limit Open ⇒ Manually reset the roll-out limit and check for a Bad Inducer Blower Wheel or a Bad Heat Exchanger.
2. Check Temperature Rise
- Initiate a call for heat (Reset the control if necessary by cycling power.)
- Ensure that the burners fire and the blower motor starts withing 60 seconds.
- Burners + No Blower Operation ⇒ Check for 24VAC between 73A (PR) and Gnd after the burners light.
- Power + No Blower = Bad Blower Motor
- No Power = Bad Ignition Control Board
- Monitor the heat exchanger temperature rise.
- Temperature Rise > Furnace Rating → Step 3. Check Filter
- Temperature Rise < Furnace Rating + Limit Opens = Bad Limit
3. Check Air Filter
- Remove the air filter and re-check the temperature rise.
- Temperature Rise Becomes Normal = Clogged or Under-Sized Air Filter
- Temperature Rise Still > Furnace Rating → Step 4. Check Gas Pressure
4. Check Gas Pressure
- Activate a call for heat and monitor the manifold gas pressure when the gas valve opens.
- Natural Gas = 2.5" w.c. minimum to 3.5" w.c. maximum
- LP Gas = 9" w.c. minimum to 11" w.c. maximum
5. Check Duct Static/Blower Speed
- Check the return static pressure (in the blower door if possible).
- Check the supply static pressure.
- High Duct Static = Above 0.5" w.c.
- High Return Static + Low Supply Static = Restricted Return Ductwork or Clogged Coil
- Low Return Static + High Supply Static = Restricted Supply Ductwork
- Normal Duct Static ⇒ Increase the blower speed by moving 73A (PR) at the motor from Terminal 4 (Med Hi) to Terminal 5 (Hi) and re-check the temperature rise.