TG9S/GY9S - Flashing Code 2

York Gas Furnace: TG9S/GY9S

Re: Flashing Code 2

Code 2 = Pressure switch stuck closed

The furnace pressure switch should only close when the inducer fan output is energized. If control board is not energizing the inducer fan output and the pressure switch circuit is closed, the board will flash a Code 2.

► PS1 and PS2 are wired in series, so both switches would have to be closed to cause a Code 2.

► A Code 2 will typically keep the inducer motor from starting and the gas furnace from operating.


Qty Possible Causes:
Bad PS1 & PS2 Pressure Switch
Inducer Fan Stuck On (Bad Control Board)
ADPS Switch Set Too Low


CHECKOUT:

1. Check Controller


2. Check Pressure Switch Contacts


3. ADPS Switch Setting



Article ID: 417
Last updated: 19 Nov, 2021
Revision: 5
Equipment -> Gas Furnaces -> York -> TG9S / GY9S -> TG9S/GY9S - Flashing Code 2