Predator - Ignition Control - Flashing Code 3

York Rooftop Unit: Predator DH, DM

Re: Ignition Control - Flashing Code 3

Flashing Code 3 = Inducer Pressure Switch failed to close or Tripped Roll-out.


The vent pressure switch and flame roll-out switch are wired in series. Therefore either switch open on a call for heat will generate a code 3.


Qty Possible Causes:
Bad Pressure Switch
Bad Pressure Switch Hose
Bad Inducer Motor
Clogged Pressure Port
2 Tripped Rollout (Bad Heat Exchanger)
Bad Ignition Control


CHECKOUT:

1. Check Control Board/Inducer


2. Check Pressure Switch


3. Check Rollout Switch



Article ID: 413
Last updated: 14 Dec, 2018
Revision: 10
Equipment -> Rooftop Units -> York -> Predator DH, DM, -> Predator - Ignition Control - Flashing Code 3