AHX/MX Air Handler - Flashing Code 5

York Air Handler: AHX / MX

Re: Flashing Code 5

Code 5 = Multiple Extended Limit Trips


A Fault Code 5 is generated from the following sequence of conditions:


Qty Possible Causes:
Bad Limit(s)
Bad Blower Motor
Missing or Loose Molex Plug
Stuck Heat Relay
Bad Heater Board

Checkout:

1. Check for Water on Control Board


2. Check Limits & Board


3. Check Blower Operation


4. Check Heat Relays



Article ID: 405
Last updated: 6 Feb, 2023
Revision: 6
Equipment -> Heat Pumps -> York -> Air Handlers -> AHX/MX -> AHX/MX Air Handler - Flashing Code 5