TM9T - Flashing Code 3

York Gas Furnace: TM9T

Re: Flashing Code 3

Code 3 = The normally open (1LP or 3LP) pressure switch contact did not close after the inducer was energized.

► This is a "Soft Lockout" which will automatically reset after 1 hour.

► There are 3 pressure switches on this furnace. 1LP (1st Stage Switch) and 3LP (Condensate Switch) are wired in series to the pressure switch input.

► The 2LP (2nd Stage Switch) wires in separately and will cause a Code 13.


Qty Possible Causes:
1 Bad Inducer Motor or Capacitor
Water in Vent
4 Water in Inducer/Clogged Drain
1 Improper Condensate Drainage
Bad Pressure Switch
Water in Pressure Switch / Tubing


CHECKOUT:

1. Check Inducer Motor Operation


2. Check Pressure Switches


3. Check Condensate Drainage



Article ID: 392
Last updated: 21 Dec, 2020
Revision: 16
Equipment -> Gas Furnaces -> York -> TM9T -> TM9T - Flashing Code 3